TPW Logo
PRODUCTS
Login

Item No. Digital Input-Field Terminal Assembly

DI_FTA

1 of 3
General Information +
Product TypeDI FTA (Field Terminal Assembly)
No Of Channels32
Hardware Functional Status From July 22
Electrical Properties +
Operating Voltage ≤ 30 V DC
Current Per Branch 1 A
Current (Terminal Block) 5 A
Input Data +
Nominal Input Voltage24 V Dc
Input Voltage Range 19.2 V DC ... 26.4 V DC
Typical Input Current At20 mA
Typical Response Time8 ms
Typical Release Time10 ms
Protective Circuit Freewheeling Diode
Output Data +
Contact Switching Type 1 Changeover Contact
Contact Material AgNi
Maximum Switching Voltage250 V AC/DC
Minimum Switching Voltage12 V
Limiting Continues Current3.15 ( Limited Fuse)
Minimum Switching Current10 mA AT 12 V
Error Detection Line Break Short CircuitNo
Connection Data (Control Level) +
Connection In Acc. With Standard IEC 60603-13
Connection Method 37 Pin D-Sub Connector
Number Of Connection1
Connection Data (Field Level) +
Connection Method Double Through, Plug In Screw Terminal
Number Of ConnectionFor 32 Channels
Conductor Cross Section Rigid 0.2 mm² ... 4 mm²
Conductor Cross Section Flexible0.2 mm² ... 2.5 mm²
Tightening Torque 0.5 Nm ... 0.6 Nm
Connection Data (Supply Level) +
Connection MethodPlug In Screw Terminal
Number Of Connection4
Conductor Cross Section Rigid0.2 mm² ... 2.5 mm²
Conductor Cross Section Flexible0.2 mm² ... 2.5 mm²
Tightening Torque0.5 Nm ... 0.6 Nm
Dimension +
Width 450 Mm
Height120 Mm
Depth70.5 mm
Material Specification +
ColorGreen
Housing Insulation MaterialPVC
Ambient Condition +
Degree Of Protection IP00
Degree Of Protection (Installation Location) ≥ IP54
Ambient Temperature -20 °C ... 70 °C
Altitude≤ 2000 m
Mounting +
Mounting Type Din Rail Mounting
Mounting PositionAny

Introducing A Revolution In Panel Wiring With Our Highly Advanced Field Terminal Assembly Fta Engineered For Superior Functionality Our Fta Enables Direct Connection Of Prefabricated Cables To The Digital Input Module Optimizing Field Connections With Unparalleled Efficiency In Your Facility This Fta Module Is Equipped With An Interposing Relay On All Channels Ensuring Complete Isolation From Field Devices To Enhance System Integrity And Safety.