 16 Channel Analog Input Module
16 Channel Analog Input Module
 16 Channel Analog Input Module
16 Channel Analog Input Module
General Information +
Number of channels 16 Channels
Type Of Analog Inputs 0/4-20 mA 12 Nos 0/4-20 mA 4 Nos. mA/Voltage Selectable
Hardware Functional Status From July 22
Firmware Version 1.00.001
Firmware Update Possible Yes
Engineering Software CODESYS V3.5 SP19 and above
Mounting Base Unit TBUS-PPPPPPPP
Type Of Analog Input 0/4-20 mA 14 Nos 0/4-20 mA 2 Nos. mA/Voltage Selectable
Isolation and Protection +
Galvanic Isolation Yes
Galvanic Isolation Groups 04 Groups 01 Group 04 Group 04 Groups
Channels In One Group 04 Channels/ Group 04 Channel/Group
Output Short-Circuit Protection Yes, For Each Channels
Input Over-Current Protection Yes (40 mA) Yes (40 mA) Yes (40 mA) Yes
Channels In Groups 16 Channel/groups
Input Short Circuit Protection Yes, For Each Channels
Channel In One Group 04 Channel/Group
Input Short-Circuit Protection Yes, For Each Channel (For mA Channel only) Yes For Each Channel (For mA Channel only)
Power Supply +
Power Supply From Top Side De-Coded Plug-In Screw Terminal
Normal Supply Voltage 24 V DC
Low Supply Voltage 21.6 V DC
High Supply Voltage 26.5
Reverse Polarity Protection Yes
Input Current 0.5 A 0.5 AMP 0.5 A 0.5 A
Input Current Per Channels (Permissible) 25 mA
Transmitter Power Yes
Power Loss Less than 1 W
Input Current Per Channel (Permissible) 25 mA 25 mA 25 mA
Range +
Input Range 0-10 V DC 4-20 mA 0-10 mA 0-10 mA
Measuring Range Scalable
Input Resistance 120 Ω in mA selection
Input Impedance 10k ohm in Voltage Selection 10k ohm in Voltage Selection
Configuration In Running +
Parameterization in Run Yes
Calibration in Run Yes
Hardware Configuration +
Automatic Encoding No
Mechanical Coding Element Yes
Conversion Principle +
Analog Input Measuring Principle Sigma Delta (Integrating) Sigma Delta (Integrating)
Analog Input Measuring Principal Sigma Delta (Integrating)
Integration And Conversion Time Per Channel +
Resolution (with over-range) 12 Bit 12 Bit 12 Bit
Conversion Time Per Channels 100 ms
Resolution (With Over Range Max) 12 Bit
Conversion Time Per Channel 100 Ms
Conversion Time Per Chennal 100 ms 100 ms
Error +
Linearity Error 0.1% (Input Range)
Operational Error 0.5% (Input Range)
Basic Error 0.3% (Input Range)
Interference Voltage Separation +
Series Mode Interference Min 70 dB
Common Mode-Voltage Max 10 V
Common Mode Interference 90 dB
Common Mode Voltage Max 10 V Max 10 V Max 10 V
Alarm +
Dignotics Alarm Yes
Limit Alarm Yes Yes Yes
Diagnostic Alarm Yes
Diagnostics Alarm Yes
Diagnostic +
Function Of Diagnostic Available Available Available
Module Fuse Blown Indication Yes
Function Of Diagnostics Available
Diagnostic Messages +
Wire-Break Yes (4-20 mA)
Short Circuit Yes Yes (For mA Channel Only) Yes (for mA Channel Only)
Channels Diagnostic Yes
Short-Circuit Yes
Channel Diagnostics Yes Yes
Channel Diagnostic Yes
LED +
Power Indication Yes
Channels Status No
Channels Diagnostics (Wire-Break) No
Module Diagnostics (Back-Plane Comm) Yes
Channel Status No No No
Channel Diagnostics (Wire-Break) No No
Channel Diagnostics (Wire-Break Joint) No
Potential Separation +
Separation Between Channels Yes (Group Isolation) in Group of 4 Channels. No Yes (Group Isolation) In Group of 4 channel Yes (Group Isolation) In Group of 4 channels
Separation Between Backplane Yes
Separation Between Channels and System Power Supply Yes
Insulation Tested With 500 V DC
Separation Between Channel and System Power Supply Yes Yes Yes
Ambient Condition +
Horizontal Installation 60°C
Vertical Installation 60°C
Connection +
Field Connection 37-Pin D-Sub Female Connector
Power Connection 5 Pin Phoenix Plug-In Screw Connector (De-Coded)
Other Information +
Cable Length Max. 500 m, 1.0 mm² shielded cable
Address Space Per Module 32 Bytes
Dimensions (W x H x D) 25 x 122 x 115 mm
Weight 160g Approx
Conversion Principal +
Analog Input Measuring Principle Sigma Delta (Integrating)