| Number of channels |
16 Channels |
32 Channels |
16 Channels |
| Hardware Functional Status |
From July 22 |
| Firmware Version |
1.00.001 |
| Firmware Update Possible |
Yes |
| Engineering Software |
CODESYS V3.5 SP19 and above |
| Mounting |
Base Unit TBUS-PPPPPPPP |
| Galvanic Isolation |
Yes |
| Galvanic Isolation Groups |
2 |
4 |
— |
| Channels in Group |
8 |
| Galvanic Isolation Group |
— |
— |
4 |
| DO |
Yes |
Yes |
— |
| DO With Energy Saving Function |
No |
No |
— |
| PWM |
No |
No |
— |
| Digital Inputs |
— |
— |
Yes |
| Counter |
— |
— |
No |
| Power Supply From |
Top Side De-Coded Plug-In Screw Terminal |
| Normal Supply Voltage |
24 V DC |
| Low Supply Voltage |
21.6 V DC |
| High Supply Voltage |
26.5 |
| Reverse Polarity Protection |
Yes |
| Maximum Current |
100 mA (Field Current not Included) |
100 mA (Field Current not Included) |
100 mA |
| Power Loss |
0.75 W |
| Automatic Encoding |
No |
| Mechanical Coding Element |
Yes |
| Number Of Digital Inputs |
32 Channel |
32 Channel |
— |
| Type Of Digital Output |
Source Output |
Source Output |
— |
| Current Sinking |
No |
No |
— |
| Current Sourcing |
Yes |
Yes |
— |
| Digital Output Parameterizable |
Yes |
Yes |
— |
| Short Circuit Protection |
Yes |
Yes |
— |
| Response Threads hold |
1 A |
1 A |
— |
| Open Circuit Detection |
Yes |
Yes |
— |
| Controlling a Digital Output |
Yes |
Yes |
— |
| Switching Capacity to Resistive Load |
0.5 A |
0.5 A |
— |
| Switching Capacity to Inductive Load |
5 W |
5 W |
— |
| For "1" Signal |
0.1 mA |
0.1 mA |
— |
| From 0 To 1 |
Max 50 µs |
Max 50 µs |
— |
| From 1 To 0 |
Max 100 µs |
Max 100 µs |
— |
| Uprating |
No |
No |
— |
| Redundant Control of Load |
Yes (using suitable FTA) |
Yes (using suitable FTA) |
— |
| Resistive Load |
100 Hz |
100 Hz |
— |
| Inductive Load |
2 Hz |
2 Hz |
— |
| Lamp Load |
10 Hz |
10 Hz |
— |
| Per Channel |
0.5 A |
0.5 A |
— |
| Per Module |
16 A |
16 A |
— |
| 30 Degree Celsius |
16 A |
16 A |
— |
| 40 Degree Celsius |
14 A |
14 A |
— |
| 50 Degree Celsius |
12 A |
12 A |
— |
| 60 Degree Celsius |
8 A |
8 A |
— |
| 30 Degree Celsius |
16 A |
16 A |
— |
| 40 Degree Celsius |
12 A |
12 A |
— |
| 50 Degree Celsius |
8 A |
8 A |
— |
| Function Of Diagnostic |
Yes |
Yes |
— |
| Diagnostic Alarm |
Available |
Available |
— |
| Module Fuse Blown Indication |
Yes |
Yes |
— |
| Diagnostic Info Readable |
Yes |
Yes |
— |
| Supply Voltage Monitoring |
Yes |
Yes |
— |
| Group Error |
Yes |
Yes |
— |
| Power Of Indication |
Yes |
| Channel Status |
Yes |
| Channel Diagnostics |
No |
No |
— |
| Module Diagnostics |
Yes |
Yes |
— |
| Fuse-Blown |
— |
— |
Yes |
| Back-Plane Communication |
— |
— |
Yes |
| Separation Between Channel |
Yes, In Group of 8 Channel |
Yes, In Group of 8 Channel |
Yes in Group Of 8 Channel |
| Separation Between Backplane |
Yes |
| Separation Between Channel And System Power Supply |
Yes |
| Insulation Tested With |
500 VDC |
| Horizontal Installation |
60°C |
| Vertical Installation |
60°C |
| Field Connection |
37-Pin D-Sub Female Connector |
| Power Connection |
5 Pin Phoenix Plug-In Screw Connector (De-Coded) |
| Cable Length Max. |
500 m |
| Address Space Per Module |
2 Bytes |
| Dimensions (W x H x D) |
25 x 122 x 115 mm |
| Weight |
140g Approx |
| Conformal Coating |
G1, G2 And G3 |
G1, G2 And G3 |
— |
| Number Of Digital Inputs |
— |
— |
32 |
| Digital Input Parameterizable |
— |
— |
Yes |
| Source Sink Input |
— |
— |
Sink/Source |
| Input Characteristics Curve As Per IEC-61131 |
— |
— |
Yes |
| Rated Voltage |
— |
— |
24 V DC |
| For 0 Signal |
— |
— |
Up to 5 V DC |
| For 1 Signal |
— |
— |
15 V DC To 28 V DC |
| For "1" Signal |
— |
— |
2 mA (max 20 mA) |
| Parameterizable |
— |
— |
Yes |
| From 0 To 1 |
— |
— |
Max 0.5 ms |
| From 1 To 0 |
— |
— |
Max 15 ms |