TPW Logo
PRODUCTS
Login

Item No. S730-07C01CV02G04GIND

08 Channel Analog Input Module

1 of 3
General Information +
No. of Analog Input 08 Channels
Type Of Analog Input07 Channels 0-20 mA 01 Channels 0-20 mA Or 0-10 V DC Selectable
Hardware Functional Status From July 22
Firmware Version1.00.001
Firmware Update Possible Yes
Engineering SoftwareCODESYS V3.5 SP19 and above
MountingBase Unit TBUS-PPPPPPPP
Isolation +
Galvanic Isolation Yes
Galvanic Isolation Group 2
Channels In Group4
Power Supply +
Power Supply FromTop Side De-Coded Plug-In Screw Terminal
Normal Supply Voltage24 V DC
Low Supply Voltage18.5 V DC
High Supply Voltage28.5
Reverse Polarity ProtectionYes
Input Current0.4 A
Input Current Per Channels Permissible21.5 mA
Transmitter Power Yes
Power Loss Less than 1 W
Range +
Input Range0-20 mA
Input Range4-20 mA
Input Range 0-10 V DC
Measuring RangeScalable
Input Resistance120 Ω in mA selection
Configuration In Running +
Parameterization in Run Yes
Calibration in Run Yes
Hardware Configuration +
Automatic EncodingNo
Mechanical Coding Element Yes
Conversion Principle +
Analog Input Measuring Principal Sigma Delta Integrating
Integration And Conversion Time Per Channel +
Resolution (with over-range)12 Bit
Conversion Time per Channel100 ms
Error +
Linearity Error 0.1% (Input Range)
Operational Error0.5% (Input Range)
Basic Errer0.3% (Input Range)
Interference Voltage Separation +
Series Mode InterferenceMin 70 dB
Common Mode VoltageMax 10 V
Common Mode Interference 90 dB
Alarm +
Diagnostics AlarmYes
Limit Alarm Yes
Diagnostic +
Function Of DiagnosticAvailable
Diagnostic Messages +
Wire-Break Yes (4-20 mA)
Short CircuitYes
Channels DiagnosticYes
LED +
Power Of IndicationYes
Channels StatusNo
Module Fuse BlownYes
Module Diagnostics (Back-Plane Comm)Yes
Potential Separation +
Separation Between Channels Yes (Group Isolation)
Separation Between BackplaneYes
Separation Between Channels And System Power SupplyYes
Insulation Tested With500 V DC
Ambient Condition +
Horizontal Installation 0°C
Horizontal Installation 60°C
Vertical Installation 0°C
Vertical Installation 60°C
Connection +
Field Connection37-Pin D-Sub Female Connector
Power Connection5 Pin Phoenix Plug-In Screw Connector (De-Coded)
Other Information +
Cable Length Max.500 m, 1.0 mm² shielded cable
Address Space Per Module 16 Bytes
Dimension (W x H x D) 25 x 122 x 115 mm
Weight 160g Approx

The analog input module is a crucial component designed to facilitate the integration of analog signals into the PLC system. It receives analog signals from a diverse array of external devices, including sensors, transmitters, gauges, variable frequency drives (VFDs), thermocouples, and transducers. Through these inputs, we are able to optimally control and monitor vital processes within the plant environment. This product is an 8-channel analog input module, designed with galvanic isolation across two distinct groups, each comprising four channels.