Item No. S73008C00CV01G08GIND

08 Channel Analog Input Module

1 of 3
General Information +
No. of Analog Inputs08 Channels
Type Of Analog Inputs 0-20 mA
Hardware Functional StatusFrom July 22
Firmware Version1.00.001
Firmware Update Possible Yes
Engineering SoftwareCODESYS V3.5 SP19 and above
MountingBase Unit TBUS-PPPPPPPP
Isolation +
Galvanic Isolation Yes
Galvanic Isolation Group 01
Channels In Group 08
Power Supply +
Power Supply FromTop Side De-Coded Plug-In Screw Terminal
Normal Supply Voltage24 V DC
Low Supply Voltage 18.5 V DC
High Supply Voltage 28.5
Reverse Polarity Protection Yes
Input Current 0.4 A
Input Current Per Channels Permissible21.5 mA
Transmitter Power Yes
Power LossLess than 1 W
Range +
Input Range 0-20 mA
Input Range 4-20 mA
Measuring Range Scalable
Input Resistance 120 Ω in mA selection
Configuration In Running +
Parameterization in Run Yes
Calibration in Run Yes
Hardware Configuration +
Automatic EncodingNo
Mechanical Coding Element Yes
Conversion Principle +
Analog Input Measuring Principal Sigma Delta Integrating
Integration And Conversion Time Per Channels +
Resolution (with over-range) 12 Bit
Conversion Time Per Channel100 ms
Error +
Linearity Error0.1% (Input Range)
Operational Error0.5% (Input Range)
Basic Error0.3% (Input Range)
Interference Voltage Separation +
Series Mode InterferenceMin 70 dB
Common Mode VoltageMax 10 V
Common Mode Interference 90 dB
Input Current +
For “1” Signal Yes
For “1” Signal Yes
Diagnostic +
Function Of Diagnostic Available
Diagnostic Messages +
Wire-BreakYes (4-20 mA)
Short-Circuit Yes
Channels Diagnostic Yes
LED +
Power Of Indication Yes
Channels StatusNo
Module Fuse Blown Yes
Module Diagnostics (Back-Plane Comm) Yes
Potential Separation +
Separation Between ChannelsYes (Group Isolation)
Separation Between BackplaneYes
Separation Between Channels And System Power SupplyYes
Insulation Tested With500 V DC
Ambient Condition +
Horizontal Installation 0°C
Horizontal Installation 60°C
Vertical Installation 0°C
Vertical Installation 60°C
Connection +
Field Connection37-Pin D-Sub Female Connector
Power Connection 5 Pin Phoenix Plug-In Screw Connector (De-Coded)
Other Information +
Cable Length Max.500 m, 1.0 mm² shielded cable
Address Space Per Module 16 Bytes
Dimensions (W x H x D)25 x 122 x 115 mm
Weight160g Approx

The analog input module is a crucial component designed to facilitate the integration of analog signals into the PLC system. It receives analog signals from a diverse array of external devices, including sensors, transmitters, gauges, variable frequency drives (VFDs), thermocouples, and transducers. Through these inputs, we are able to optimally control and monitor vital processes within the plant environment. This product is an 8-channel analog input module, designed with galvanic isolation across two distinct groups, each comprising four channels.