Item No. S730-08C00CV01G08GIND

08 Channel Analog Input Module

1 of 3
General Information +
Number of channels 08 Channels
Type Of Analog Inputs 0-20 mA
Hardware Functional Status From July 22
Firmware Version 1.00.001
Firmware Update Possible Yes
Engineering Software CODESYS V3.5 SP19 and above
Mounting Base Unit TBUS-PPPPPPPP
Isolation +
Galvanic Isolation Yes
Galvanic Isolation Group 01
Channels In Group 08
Power Supply +
Power Supply From Top Side De-Coded Plug-In Screw Terminal
Normal Supply Voltage 24 V DC
Low Supply Voltage 18.5 V DC
High Supply Voltage 28.5
Reverse Polarity Protection Yes
Input Current 0.4 A
Input Current Per Channels Permissible 21.5 mA
Transmitter Power Yes
Power Loss Less than 1 W
Range +
Input Range 0-20 mA
Input Range 4-20 mA
Measuring Range Scalable
Input Resistance 120 Ω in mA selection
Configuration In Running +
Parameterization in Run Yes
Calibration in Run Yes
Hardware Configuration +
Automatic Encoding No
Mechanical Coding Element Yes
Conversion Principle +
Analog Input Measuring Principal Sigma Delta Integrating
Integration And Conversion Time Per Channels +
Resolution (with over-range) 12 Bit
Conversion Time Per Channel 100 ms
Error +
Linearity Error 0.1% (Input Range)
Operational Error 0.5% (Input Range)
Basic Error 0.3% (Input Range)
Interference Voltage Separation +
Series Mode Interference Min 70 dB
Common Mode Voltage Max 10 V
Common Mode Interference 90 dB
Input Current +
For “1” Signal Yes
For “1” Signal Yes
Diagnostic +
Function Of Diagnostic Available
Diagnostic Messages +
Wire-Break Yes (4-20 mA)
Short-Circuit Yes
Channels Diagnostic Yes
LED +
Power Of Indication Yes
Channels Status No
Module Fuse Blown Yes
Module Diagnostics (Back-Plane Comm) Yes
Potential Separation +
Separation Between Channels Yes (Group Isolation)
Separation Between Backplane Yes
Separation Between Channels And System Power Supply Yes
Insulation Tested With 500 V DC
Ambient Condition +
Horizontal Installation 0°C
Horizontal Installation 60°C
Vertical Installation 0°C
Vertical Installation 60°C
Connection +
Field Connection 37-Pin D-Sub Female Connector
Power Connection 5 Pin Phoenix Plug-In Screw Connector (De-Coded)
Other Information +
Cable Length Max. 500 m, 1.0 mm² shielded cable
Address Space Per Module 16 Bytes
Dimensions (W x H x D) 25 x 122 x 115 mm
Weight 160g Approx

The analog input module is a crucial component designed to facilitate the integration of analog signals into the PLC system. It receives analog signals from a diverse array of external devices, including sensors, transmitters, gauges, variable frequency drives (VFDs), thermocouples, and transducers. Through these inputs, we are able to optimally control and monitor vital processes within the plant environment. This product is an 8-channel analog input module, designed with galvanic isolation across two distinct groups, each comprising four channels.